Download new and previously released documents including product document, solutions, cases, coporate report.
View NowReach out to us to receive more information, technical support, assistance with complaints and more.
Get SupportWhat is the main application of the CB-125CXZ MCCB?
It is designed for DC systems up to 80 V, providing overload and short-circuit protection for industrial and telecommunication power lines.
How does the CB-125CXZ differ from the CB-125CX model?
While both share the same frame and trip characteristics, the CB-125CXZ is specifically rated for DC 80 V, whereas the CB-125CX is for AC up to 415 V.
What is the short-circuit breaking capacity of this MCCB?
It features a 10 kA breaking capacity for both Icn and Ics, ensuring dependable interruption capability in DC circuits.
What installation method does it use?
The breaker adopts a plug-in installation design for quick and secure mounting, with bottom feeding for straightforward wiring.
Can the CB-125CXZ operate in harsh environments?
Yes. It operates reliably from −40 °C to +70 °C, up to 2 000 m altitude, and features IP20/IP40 protection with UL94 V-0 flame-retardant materials, ensuring performance in demanding industrial environments.