Get SupportWhat is the main function of the CB-63DC MCCB?
It provides overload, short-circuit, and isolation protection for DC power systems up to 500 V, ensuring safety and operational reliability.
What trip characteristic does it use?
The CB-63DC uses a thermomagnetic trip unit with Curve C (8.5 × In ± 20%), offering fast, precise response for general DC circuit protection.
What are the available configurations?
It comes in 1P and 2P configurations with rated voltages of 250 V DC and 500 V DC respectively.
How durable is it?
The CB-63DC delivers a mechanical life of 20,000 operations and electrical life of 6,000 operations, ensuring long-term reliability.
In which environments can it operate?
It operates in temperatures from −35 °C to +70 °C and altitudes up to 2000 m, with an IP20/IP40 protection rating for safe installation.