NGH7-12 Eco-Friendly GIS for Secondary Distribution
An Ring Main Unit designed, manufactured and fully type-tested according to IEC 62271-200, NGH7 is widely used in power distribution systems, such as utilities, industries, buildings and new energy power stations.
An Ring Main Unit designed, manufactured and fully type-tested according to IEC 62271-200, NGH7 is widely used in power distribution systems, such as utilities, industries, buildings and new energy power stations.
- Dry air gas-insulated switchgear
- For secondary distribution
- 12kV, 630A, 25kA
Customer Benifits:
- Environmentally friendly
- Safe & Reliable
- Maintenance free
- Small in size
- Easy to install
- Smart function
Technical Specifications
NGH7-12
NGH7-24
NGH7-24 2.0
NGH-12(Z)
NGH-24(Z)
NGH-40.5(Z)
Type of Switch
CB
CB, LBS
CB, LBS, LBS+Fuse
CB
CB
CB
Rated Voltage (kV)
12
24
24
12
24
40.5
Rated Current (A)
630
630
630
1250~3150
1250
1250~2500
Rated Frequency (Hz)
50
50/60
50/60
50
50/60
50
Withstand Voltage (kV)
42/75
65/125
50/125
42/75
65/125
95/185
Short Time Current (kA/s)
20/4
21/3
21/3
31.5, 40/4
25/4
31.5/4
Peak Withstand Current (kA)
50
54.6
54.6
80, 100
65
80
IAC (kA/s)
AFLR 20/0.5
AFL 21/1
AFLR 21/1
AFLR 31.5, 40/1
AFLR 25/1
AFLR 31.5/1
Rated / Min. Gas Pressure(MPa, Rel.)
0.02 / 0
0.05 / 0.03
0.08 / 0.06
0.02 / 0
0.05 / 0.025
0.05 / 0.02
Altitude (m)
≤4500
≤3000
≤1500
≤4500
≤4500
≤4500
Dimension (mm, W*D*H)
420*850*2000
450/400*845*1635
(without LV box)
420/400*780*1400
(without LV box)
600*1400*2400
/800*1700*2400
600*1230*2250
800/1000*2263*2550
Applicable Standards
IEC, GB
Applications
Power distribution
Renewable energy
Infrastructure
Data center
Industrial electricity
Customer Value
Eco-Friendly
Dry air fully replaces SF6 with GWP=0. Eliminates greenhouse gas emissions and removes environmental compliance risks, supporting your carbon neutrality goals.
Highly Reliable
Optimized insulation design ensures stable switching and insulation performance even at gas leakage conditions at rated voltage.
Convenient & Flexible
Modular compartment construction enables plugand-play onsite assembly with no gas handling required, speeding up installation and allowing easy future expansion.
Safe
Comprehensive mechanical interlocking design effectively avoids the adverse impact on the system caused by misoperation.
Maintenance Free
All active and switching parts are fully sealed and insulated, no maintenance cycle needed, saving maintenance time and cost.
Learn how shunt reactors absorb reactive power to manage voltage rise on lightly loaded lines, and what engineers should consider when selecting and applying them.
Learn how current transformers (CTs) and voltage transformers (VTs) support metering and protection, and what to consider when selecting and installing them.
Learn how a phase monitoring relay detects phase loss and phase reversal, how it should be wired into a motor control circuit, and where its protection ends.
Choose a DIN rail power supply for an industrial control panel by checking output load, inrush, environmental derating, protection and PLC compatibility.
A capacitor bank does not switch like a motor load. Learn how dedicated capacitor switching contactors manage inrush, switching duty and protection in power factor correction panels.
Learn how to select and wire a control relay for an industrial panel, including coil voltage, contact form, load rating, suppression, and CHINT NXJ and NJX12 options.
Select an electromagnetic starter for OEM panels by checking motor duty, AC-3 ratings, protection coordination, control options, enclosure, and mounting.
Understand reactive power compensation, how static VAR generators differ from SVC systems, and where CHINT NXW APF and SVG modules fit in industrial power systems.