A Ring Main Unit designed, manufactured and fully type-tested according to IEC 62271-200, NG7 is widely used in power distribution systems, such as utilities, industries, buildings and new energy power stations.
Application: ring network power supply or dual radiant power supply
for 12~40.5kV power supply line.
Standards: IEC62271-200
IEC62271-10
IEC62271-1
Parameters: 12~40.5kV
Features: Adapt to operation environment
High level of protection
Compact structure
Flexible expansion
Maintenance free
Operation reliability
Technical Specifications
NG7-12
NG7-17.5
NG7-24
NG7-40.5
NG7-12(Z)
NG7-27,5(Z)
NG7-40.5(Z)
Type of switch
CB, LBS, LBS+Fuse
CB, LBS
CB, LBS, LBS+Fuse
CB, LBS
CB
CB
CB
Rated voltage (kV)
12
17.5
24
40.5
12
1*27.5 / 2*27.5
40.5
Rated current (A)
630
400
630
630 / 1250
1250~3150
1250 - 1P
2500 - 1P or 2P
1250~4000
Rated frequency (Hz)
50
60
50/60
50/60
50
50
50
Withstand voltage (kV)
42/75
38/95
65/125
95/185
42/75
95/200
95/185
Short time current (kA/s)
25/4
21/1
20/4
25~31.5/4
25~40/4
31.5/4
31.5~40/4
Peak withstand current (kA)
63
54.6
52
65~80
63~100
80
80~100
IAC (kA/s)
AFLR 25/1
AFLR 21/1
AFLR 20/1
AFLR 25/1
AFLR 31.5/1
AFLR 31.5/1
AFLR 31.5/1
Rated / Min. gas pressure(MPa, Rel.)
0.04 / 0.02
0.04 / 0.02
0.04 / 0.02
0.04 / 0.02
0.03 / 0
0.03 / 0
0.04 / 0.01
Altitude (m)
≤ 4500
≤ 4500
≤ 4500
≤ 4500
≤ 4500
≤ 4500
≤ 4500
IP degree (Gas tank / Enclosure / Outdoor)
IP67 / IP4X / IP54
IP67 / IP4X / IP54
IP67 / IP4X / IP54
IP67 / IP4X / IP54
IP67 / IP4X
IP67 / IP4X
IP67 / IP4X
Applicable Standards
IEC,IEEE, GB
Applications
Power distribution
Renewable energy
Infrastructure
Data center
Industrial electricity
Customer Value
Safe & Reliable
Comprehensive mechanical interlocking design effectively avoids the adverse impact on the system caused by misoperation.
Maintenance Free
All active and switching parts are fully sealed and insulated, no maintenance cycle needed, saving maintenance time and cost.
Convenient & Flexible
Modular compartment construction enables plugand-play onsite assembly with no gas handling required, speeding up installation and allowing easy future expansion.
Harsh-environment Resistant
Optional Zn-Ni alloy components and premium coating improve salt spray resistance. IP54 enclosure is available for outdoor deployment.
Choose a DIN rail power supply for an industrial control panel by checking output load, inrush, environmental derating, protection and PLC compatibility.
A capacitor bank does not switch like a motor load. Learn how dedicated capacitor switching contactors manage inrush, switching duty and protection in power factor correction panels.
Learn how a phase monitoring relay detects phase loss and phase reversal, how it should be wired into a motor control circuit, and where its protection ends.
Learn how industrial energy monitoring turns meter data into lower energy waste and stronger power reliability, with CHINT DTSU666-CT and PD7777 options.
Learn how to select and wire a control relay for an industrial panel, including coil voltage, contact form, load rating, suppression, and CHINT NXJ and NJX12 options.
Select an electromagnetic starter for OEM panels by checking motor duty, AC-3 ratings, protection coordination, control options, enclosure, and mounting.
Understand reactive power compensation, how static VAR generators differ from SVC systems, and where CHINT NXW APF and SVG modules fit in industrial power systems.
Voltage fluctuation quietly damages industrial equipment. Learn how a three-phase voltage stabilizer works and why independent phase regulation matters for generator-backed power.