Rated operation voltage Ue: AC 240V, 50Hz; Overvoltage operation setting value Uvo: 280V; Rated insulation voltage Ui: 500V; Tripping characteristics: the release is assembled with NXB-63 series circuit breaker. When the applied voltage is reduced to 35%Ue or increased to 95% ~ 105% of the over-voltage setting value, the release should drive the circuit breaker to act. When the applied voltage is below 35%Ue or above 105% of the over-voltage setting value, the release should be able to prevent the circuit breaker from closing. When the supply voltage is above 85% Ue and below 95% of over-voltage setting value, the circuit breaker should be able to close normally. The upper limit of the applied voltage should be less than 110% over-voltage operation setting value. Mechanical and electrical life: the mechanical and electrical life after the release is assembled with the circuit breaker should be ≥ 4000 cycles, of which, 500 cycles for over-voltage trip and under-voltage trip each, and 3000 cycles for the open/close of the circuit breaker.
Explore key principles and parameters of transformer design, ensuring efficiency, reliability, and optimized performance for diverse electrical applications.
Cooling methods for transformers include ONAN, ONAF, and OFAF, among others, which use thermal and fluid dynamics to adjust core and winding temperatures under different load circumstances.