Por favor, introduzca palabras clave para buscar

Global |EN

Elige tu país e idioma

Asia Pacífico

Australia y Nueva Zelanda
India
Indonesia
Corea
Malasia
Filipinas
Singapur
Singapur (luz del sol)
Vietnam

Oriente Medio y África

CHINT-EGEMAC
Arabia Saudita
Sudáfrica
Emiratos Árabes Unidos
CHINT AJLAN

Europa

España
Francia
Kazajstán
Italia
Netherlands
Pavo
Reino Unido

América del norte

México

América Latina

Brasil
Colombia
Ecuador
Perú
Baja tensión
Aparatos de conmutación de baja tensión y software
Carga de vehículos eléctricos
Telecomunicaciones y Data centers
Edificios
Centro de servicio
Contáctenos
Llámanos +57 (601) 712-5419
Envíenos un correo electrónico infoco@chintglobal.com
Acerca de CHINT
Centro de noticias
Carreras

Elige tu país e idioma

Australia y Nueva Zelanda
India
Indonesia
Corea
Malasia
Filipinas
Singapur
Singapur (luz del sol)
Vietnam
CHINT-EGEMAC
Arabia Saudita
Sudáfrica
Emiratos Árabes Unidos
CHINT AJLAN
España
Francia
Kazajstán
Italia
Netherlands
Pavo
Reino Unido
México
Brasil
Colombia
Ecuador
Perú

Por favor, introduzca palabras clave para buscar

Su término de búsqueda contiene palabras clave restringidas. Utilice otras palabras clave.

Key Differences Between Air Insulated Substations and Gas Insulated Substations

FEB 21, 2025

  Table of Contents                    

  1. Construction
  2. Footprint & Suitable Environments
  3. Safety & Reliability
  4. Scalability
  5. Environmental Impact
  6. CHINT’s Insulated Switchgear for Substations
  7. Conclusion

Nowadays, the most common types of switchgear used in substations are Air Insulated Switchgear (AIS) and Gas Insulated Switchgear (GIS). While AIS uses air as insulation, GIS uses SF₆ gas in a sealed environment. They each offer unique benefits more suited to different applications. In this article, we assess the primary difference between AIS and GIS substations for five critical aspects.

 

Construction

The basic difference between AIS substation and GIS substation is the type of construction and medium of insulation involved.

  • AIS Construction: AIS uses air as the insulating medium, which exposes the electrical portions of the equipment to the surrounding environment. This typically consists of circuit breakers, disconnectors, transformers and other equipment, mounted on steel or concrete structures.
  • GIS Construction: SF₆ gas is used in GIS (Gas Insulated Switchgear) for the insulation and protection of the electrical component in a fully enclosed metal structure due to its superb dielectric properties. The bushings are potted, and the busbars, circuit breakers, and disconnectors are placed in metal-clad compartments.

Because the GIS uses a completely sealed design, it provides better protection against pollution by electromagnetic interference than AIS, which is less safety than GIS and subject to ambient conditions in the installation environment, so maintenance is required more frequently.

 

Footprint & Suitable Environments

The second difference between AIS substaitons and GIS substaitons is in their spatial requirements and adaptability to various environments.

Space Requirement

With its compact design, GIS requires significantly less space compared to other systems, making it especially suitable for urban environments, industrial facilities, and underground substations where space is at a premium. Tunnels, offshore platforms, and crowded areas are also very suitable for effective installation of GIS. AIS requires a lot of space compared to GIS because air insulation distance is required between two points. Better suited for rural or suburban areas where there is more land.

Suitable Environments

GIS is notably resilient in harsh environments, such as coastal, desert, and high-humidity regions, thanks to its enclosed structure. Conversely, AIS operates best in moderate climates where issues like contamination and extreme weather are less prevalent. This is primarily because air, as an insulating medium, is more vulnerable to fluctuations in humidity, pollution, and temperature. In environments with high humidity or pollution, the insulating properties of air can diminish, raising the risk of flashovers and necessitating extra maintenance to maintain operational reliability.

Safety & Reliability

Substations are designed with safety and reliability in mind. GIS and AIS have different ways of handling such threats.

  • GIS: Since the GIS is fully enclosed, the possibility of arc flash accidents is greatly reduced, thus protecting personnel from any direct interaction with high-voltage components. Furthermore, use of SF₆ insulation reduces risks of dielectric failures leading to enhancement of overall reliability.
  • AIS: Differently to the above, AIS is outdoor and thus susceptible to environmental conditions, which means threats from elements such as; lightning, pollution, humidity. This creates additional risks with higher maintenance needs and more constraints to mitigate those risks.

While both systems are designed to be reliable, GIS generally requires less maintenance and has fewer unexpected outages due to its sealed nature.

 

Scalability

Scalability is an important factor when considering future expansion or modifications to substation infrastructure. Different manufacturers offer varying levels of scalability for AIS and GIS substations.

  • AIS Scalability: AIS substations are relatively easier to expand. Since they are built in an open-air layout, adding additional bays, transformers, or switchgear can be done with minimal disruption to existing operations. This makes AIS a cost-effective choice for utilities planning future expansions.
  • GIS Scalability: GIS is more complex to expand due to its modular and compact design. Expanding a GIS substation typically requires adding new gas-insulated modules, which may be expensive and require specialized handling. However, leading manufacturers such as CHINT have been developing modular GIS solutions that allow for some level of scalability.

Different manufacturers offer varying GIS scalability solutions, with some emphasizing modularity and plug-and-play expansion, while others focus on integrated solutions with digital monitoring for enhanced adaptability.

 

Environmental Impact

Environmental considerations are also essential in the design of modern substations.

Gas-insulated switchgear (GIS) uses SF₆ gas, which is a potent greenhouse gas with a high global warming potential (GWP). Though GIS is designed to prevent leaks, SF₆ emissions can still result from aging equipment and mishandling — and those emissions contribute to climate change. Insulation gases with fewer or no environmental effects are being considered by manufacturers.

Air-insulated switchgear (AIS) has less environmental impact than SF₆. But it has a much bigger land footprint, which may lead to deforestation or habitat disruption in large installations.

Many power companies and regulatory bodies are promoting the use of SF₆-free solutions, pushing manufacturers to develop eco-friendly GIS alternatives using dry air or alternative gases.

CHINT’s Insulated Switchgear for Substations

Leading electrical equipment manufacturers, such as CHINT, provide GIS solutions to meet diverse power distribution needs in substation applications. Two notable GIS models from CHINT include:

  • ZFW34A-252 Gas Insulated Switchgear: A small unit suitable for both indoor and outdoor substation use. It can withstand ambient temperatures ranging from -40°C to +55°C at altitudes of up to 3000m and wind speeds of approximately 34m/s. This model is ideal for outdoor substations exposed to various climatic conditions as well as compact indoor substations requiring space efficiency.
  • ZFW21A-72.5/126/145kV Gas Insulated Switchgear: A larger unit designed for both indoor and outdoor substations. It offers similar weather resistance features but with enhanced robustness and seismic resistance up to 9 degrees. It can endure horizontal and vertical acceleration forces of approximately 0.3g m/s² and 0.15 m/s², respectively, making it well-suited for substations in seismically active regions.

These GIS solutions from CHINT ensure reliability and efficiency in modern substations, catering to the evolving demands of power distribution infrastructure.

 

Conclusion

Both AIS and GIS substations offer unique advantages and are suited for different applications. AIS is cost-effective, easier to expand, and environmentally friendly, but requires more space and frequent maintenance. GIS, on the other hand, provides a compact, reliable, and low-maintenance solution ideal for space-constrained or harsh environments, but comes with higher costs and SF₆-related environmental concerns.

Choosing between AIS and GIS ultimately depends on factors such as available space, environmental conditions, budget, and future scalability requirements. CHINT's GIS offerings provide reliable and efficient solutions for modern electrical infrastructure needs.

Lo último
MAY 6, 2025 NGC5 Diseñado para la excelencia, fabricado para la fiabilidad

NGC5 Original Manufactured LV Switchgear es el nuevo tipo de montaje de prueba elaborado por CHINT. Establece un nuevo punto de referencia para la fiabilidad y la eficiencia.

APRIL 22, 2025 Cómo protege el magnetotérmico NM8N-HV las salidas de CA de los sistemas solares

El disyuntor de caja moldeada NM8N-HV proporciona una protección esencial para las salidas de CA en sistemas de energía solar contra cortocircuitos y sobrecargas.

APRIL 15, 2025 What is a New Energy Air Switch Disconnector: Facts You Need to Know

Discover how the new energy air switch disconnector (solar disconnector switch) plays a crucial role in ensuring safety and reliability in utility-scale solar and battery energy storage systems (BESS).

APRIL 2, 2025 Experience Smooth Motor Starting with CHINT’s NJRP5-D Soft Starter

This article focuses on CHINT’s NJRP5-D Soft Starter and explores its functionality and advantages.

MARCH 26, 2025 Celda de media tensión GIS RMU CHINT 36/40,5kV: Nuevas aplicaciones energéticas con soluciones innovadoras

La celda de media tensión RMU CHINT no sólo resuelve los retos técnicos y medioambientales, sino que también mejora la eficacia operativa y la rentabilidad de los clientes.

MARCH 21, 2025 Single Phase vs Three Phase Voltage Regulator

This article explains the differences between single phase voltage regulators and three phase voltage regulators.

MARCH 18, 2025 Miniature Circuit Breaker: Understanding UL 489 and UL 1077

This article specifies the key differences between UL 489 and UL 1077, helping choose suitable Miniature Circuit Breakers.

MARCH 17, 2025 IEC frente a UL: Comprender las normas de certificación de disyuntores de aire

Compare la certificación IEC frente a la UL para disyuntores de aire: normas regionales, cumplimiento de las normas de seguridad y soluciones con certificación mundial de CHINT para una protección eléctrica fiable.

MARCH 5, 2025 Guide to Air Circuit Breaker Maintenance

This guide discovers essential inspection, cleaning, and testing procedures of the air circuit breaker to prevent failures and extend equipment lifespan.

FEBRUARY 26, 2025 The Basics of NVF2L Compact Micro Drive

NVF2L Compact Micro Drive is designed to meet the growing demand for efficient, space-saving solutions in various industrial applications. Explore CHINT's industrial drive technology solutions.