Please enter keywords to search

Global |EN

Choose your country & Language

Asia Pacific

Australia & New Zealand
India
Indonesia
Korea
Malaysia
Philippines
Singapore
Singapore (Sunlight)
Vietnam

Middle East & Africa

CHINT-EGEMAC
Saudi Arabia
South Africa
UAE
CHINT AJLAN
Egypt

Europe

France
Italy
Spain
Turkey
Kazakhstan
Netherlands

North America

Mexico

Latin America

Brazil
Peru
Ecuador

Choose your country & Language

Australia & New Zealand
India
Indonesia
Korea
Malaysia
Philippines
Singapore
Singapore (Sunlight)
Vietnam
CHINT-EGEMAC
Saudi Arabia
South Africa
UAE
CHINT AJLAN
Egypt
France
Italy
Spain
Turkey
Kazakhstan
Netherlands
Mexico
Brazil
Peru
Ecuador

Please enter keywords to search

Your search term contains restricted words. Please use different keywords.

How to Install NXR-38 Thermal Overload Relay

FEB 17, 2025

Install NXR-38 Thermal Overload Relay
Install NXR-38 Thermal Overload Relay
Install NXR-38 Thermal Overload Relay

Table of Contents

  1. Preparation
  2. Installation Steps
  3. Wiring Instructions
  4. Testing Steps
  5. Fault Diagnosis and Troubleshooting
  6. Summary

Thermal overload relays are valuable devices. They help protect electrical motors from potential damage. It’s specifically the damage caused by excessive current. The NXR-38 Thermal Overload Relay is a popular device in this category. It monitors motor current and prevents overheating. This guide provides thorough instructions for installing, commissioning, operating, and troubleshooting the NXR-38 relay. The goal is to help you ensure safe and efficient motor operation.

Preparation

Follow the following preparation steps for a smooth and safe setup of this 3 phase overload relay:

1. Safety Precautions

Always prioritize safety during installation. Disconnect the power source. Wear insulating gloves and protective goggles.

2. Tool Checklist

Here’s what you’ll need for a successful thermal overload relay installation:

  • Wire strippers
  • Crimping tools
  • Screwdrivers
  • Multimeter
  • Appropriate wires
  • Wire lugs
  • Insulated gloves
  • Protective goggles
Install NXR-38 Thermal Overload Relay
Install NXR-38 Thermal Overload Relay
Install NXR-38 Thermal Overload Relay

Installation Steps

Following these steps for proper mounting and connection of the NXR-38 Thermal Overload Relay:

1. Inspection

Before installation, verify that the STOP, RESET, and TEST buttons function normally.

2. Mounting

Carefully attach the AC contactor actuator to the DIN rail. Align the top edge first, then press down firmly to secure the bottom. Then, use a screwdriver to remove the AC contactor terminals 2/T1, 4/T2, and 6/T3.

3. Connecting the Relay

Hang the rear cover hook of the thermal overload relay into the slot of the AC contactor. Precisely align the three conductive rods of the thermal relay 1/L1, 3/L2, and 5/L3 with the terminals of the AC contactor. Press the rods into position. Then tighten the securing screws with a screwdriver.

4. Adjust Current Setting

The current setting is crucial for thermal overload protection. Calibrate the adjustment cam to match the specific working conditions of your motor.

Wiring Instructions

Proper wiring is critical to the relay’s performance and overall system reliability. Follow these recommendations and guidelines:

1. Wire Selection

Choose wires with appropriate cross-sectional areas based on the current rating. This ensures optimal electrical conductivity and safety of the overload relay thermal unit. Refer to this table for the correct selection:

Rated Current (In)

Wire Cross-Section (S (Cu) mm²)

12A

1 ~ 4

25A

1 ~ 6

38A

4 ~ 10

100A

4 ~ 35

2. Wire Preparation

Strip insulation to the specified length and crimp wire lugs securely:

  • For primary circuit wiring, strip 11 to 13 millimeters.
  • For auxiliary circuit wiring, strip 9 to 11 millimeters.

3. Wiring Guidelines

Create clear physical separation between primary and auxiliary circuits. Use cable management techniques to route wires. For NXR-38 auxiliary contact terminals 95 96 (NC or Normal Close Contact) connect in the same loop with contactor terminals A1 A2. Terminals 97 and 98 are Normal Open Contacts (NO).

Use a calibrated torque screwdriver to tighten electrical connections. Follow recommended torque values for each specific terminal type. These include:

Fastening Screw Size

M3.5

M4

Tightening Torque (N.m.)

0.8

1.7

Testing Steps

Thorough testing is essential to verify the relay’s proper installation and functionality. There are two key checks:

1. Pre-Power Check

Verify the status of the STOP, RESET, and TEST buttons before powering up the system.

2. Post-Power Test

Use a multimeter to perform continuity checks and confirm the normal operation of the thermal overload relay.

Fault Diagnosis and Troubleshooting

Despite careful installation, a thermal overload relay can occasionally encounter operational issues. The following table provides a comprehensive overview of common symptoms, their potential causes, and recommended troubleshooting methods:

Symptom

 

Potential Causes

Troubleshooting Methods

Thermal Relay Malfunctions Without Overload

 

Incorrect model selection (too small)

Replace with a larger specification product

The current value set lower than the motor’s operating current

Adjust the cam clockwise to match the actual motor current

Strong mechanical shocks or vibrations

Inspect the installation site. Ensure the relay is not in a high-impact environment

Frequent motor starts

Limit motor start frequency to 30 starts per hour

Inadequate wire connections

Use standard wire sizes. Ensure proper connection torque settings

Thermal Relay does not Operate

Incorrect model selection (too large)

Replace with a smaller specification product

The current value is set higher than the motor current

Adjust the cam counterclockwise to match the motor current

Oversized wire cross-section

Use appropriate wire sizes and also apply proper torque settings

Thermal Relay does not Operate

Relay reset mechanism failure

Press the RESET button firmly

Auxiliary contacts not conducting

Replace the thermal relay

Main or auxiliary circuit damage

Replace the thermal relay

 

Summary

Installing the NXR-38 Thermal Overload Relay requires careful preparation and precise installation. Thorough testing is crucial to ensure proper operation. By following these relay installation guidelines, you can ensure reliable motor protection and optimal performance. At CHINT, we offer reliable electrical solutions. Browse our website to access our detailed documentation.

The Latest
OCTOBER 15, 2025 Guide to MCB Trip Curves: Selecting the Right B, C, or D Curve for Overcurrent Protection

Solve nuisance tripping problems for good. Our guide helps you diagnose why your breaker trips on startup and shows how to select the correct B, C, or D curve for motors, pumps, and other loads.

SEPTEMBER 28, 2025 Industrial Diesel Generator Safety Devices That Keep Operations Running

Discover how diesel generator safety devices like MCCBs, ACBs, and relays ensure reliable backup power, protect facilities, and keep operations running safely.

SEPTEMBER 23, 2025 Manual Motor Starter: A Guide for Safer Motor Control

Every electric motor needs protection against fault conditions. In this article, learn how a manual motor starter helps you achieve this requirement.

AUGUST 22, 2025 MCCB Frame Sizes Explained: Choosing the Right Circuit Breaker for Industrial Loads

Circuit breakers are important in any electrical system. Learn about MCCB frame sizes to select the correct circuit breaker for industrial loads.

AUGUST 14, 2025 Customized Electrical Components with Better Adaptability, Better Meet Customer Needs

CHINT offers customized OEM electrical solutions with global compliance, fast delivery, and superior adaptability for HVAC, DG, and elevator applications.

AUGUST 11, 2025 From Certification to Application: How CHINT M1 MCCB Supports OEM Success Stories

CHINT M1 MCCB: UL489-certified, high-capacity, versatile breaker powering OEM success in HVAC, solar, industrial & more.

AUGUST 1, 2025 Slim RCBO Solutions for Power Distribution: CHINT NB1L-20 for Compact, Compliant Installations

CHINT’s NB1L-20 is a great addition to any power distribution system. Learn why you should consider our product if you value safety and compliance.

JULY 14, 2025 UL Certification Requirements for OEMs: Essential Guide for Renewable Energy Projects in 2025

UL Certification Requirements for OEMs: Essential Guide for Renewable Energy Projects in 2025

JULY 10, 2025 Configuration Guide: Setting Up the CHINT SMG-WSR and SMG-ESR Open Protocol Gateway

Step-by-step protocol gateway setup guide for CHINT SMG-WSR and SMG-ESR, covering wiring, network configuration, and MQTT cloud connection.

JULY 2, 2025 A Guide to the CHINT SMG Open Protocol Gateway: Building Flexible IoT Solutions

Discover how CHINT’s SMG-WSR/SMG-ESR Gateway and NB2 Circuit Breakers create smart, efficient, and remote-controlled electrical systems for various industries.