What is the main function of the OUVT-X1?
It provides automatic protection against dangerous voltage fluctuations by disconnecting the circuit breaker during over-voltage or under-voltage conditions, ensuring equipment safety.
Which circuit breakers is it compatible with?
The OUVT-X1 is designed for CHINT’s NXB-63 series circuit breakers, easily attaching to the left side of the unit for fast installation.
How does it determine trip conditions?
Trips when voltage drops below 35% Ue or exceeds 105% of the 280V over-voltage setting.
Allows breaker closure only within safe limits (85%–95% of rated voltage).
How is the OUVT-X1 installed?
It is mounted on a TH35-7.5 DIN rail, connecting directly to the NXB-63 circuit breaker. Installation is quick and requires minimal wiring adjustments.
What is its service life?
The unit has a mechanical and electrical life of over 4000 cycles, ensuring reliable long-term performance under normal and fault conditions.