Please enter keywords to search

Global |EN

Choose your country & Language

Asia Pacific

Australia & New Zealand
India
Indonesia
Korea
Malaysia
Singapore (Sunlight)
Vietnam

Middle East & Africa

CHINT-EGEMAC
Saudi Arabia
South Africa
UAE
CHINT AJLAN

Europe

France
Italy
Spain
Turkey
Kazakhstan
Netherlands

North America

Mexico

Latin America

Brazil
Peru
Ecuador

Choose your country & Language

Australia & New Zealand
India
Indonesia
Korea
Malaysia
Singapore (Sunlight)
Vietnam
CHINT-EGEMAC
Saudi Arabia
South Africa
UAE
CHINT AJLAN
France
Italy
Spain
Turkey
Kazakhstan
Netherlands
Mexico
Brazil
Peru
Ecuador

Please enter keywords to search

Your search term contains restricted words. Please use different keywords.

How to Install NS2-25 Motor Starter

FEB 11, 2025

Install NQ3 DOL Electromagnetic Starter
Install NQ3 DOL Electromagnetic Starter
Install NQ3 DOL Electromagnetic Starter

Table of Contents

  1. Necessary Tools for the Installation
  2. Steps of Installation
  3. How to Test the NQ3 DOL Starter
  4. Troubleshooting Guide
  5. Conclusion

Electromagnetic starters are critical components in industrial electrical systems. They enable efficient motor control and protection. The NQ3 DOL electromagnetic starter is a reliable solution. It’s designed for managing electrical equipment with precision and safety. This guide provides step-by-step installation instructions. The aim is to help you navigate the setup of this DOL starter with confidence.

Necessary Tools for the Installation

Installing an NQ3 DOL starter requires specific tools. Here’s what you’ll need:

  • M20×1.5 nylon waterproof wire connector
  • Screws (not less than M5)
  • Hammer
  • Wire strippers
  • Wire crimping pliers
  • Appropriate specification wires
  • Wire noses
  • Electric screwdriver
  • Flat-head screwdriver
  • Insulating gloves
  • Multimeter
NQ3 DOL Electromagnetic Starter
NQ3 DOL Electromagnetic Starter
NQ3 DOL Electromagnetic Starter

Steps of Installation

Successful installation of this DOL starter demands a systematic approach. Follow these guidelines.

1. Pre-installation Check

Before beginning the installation, verify that the motor starter model matches the intended working conditions.

Carefully select an installation location that provides adequate ventilation. It should provide protection from direct sunlight.

Minimal exposure to moisture or extreme temperatures is also ideal for direct online starters.

2. Disassembly

Carefully loosen the screws connecting the upper cover and base of the DOL starter.

Remove the upper cover and extract the protective bubble film inside the product, preparing the motor starter for installation.

3. Base Preparation and Installation

Use a flat-head screwdriver and hammer to remove knockout holes on both sides of the base.

Install the M20×1.5 nylon waterproof wire connector at the corresponding installation holes.

Make sure to select the appropriate screws to securely mount the base at the chosen installation location.

4. Wire Preparation

Select wires with the appropriate cross-sectional area based on the current rating of the direct online starter. Refer to these:

In(A)

0<|≤8

8<|≤12

12<|≤20

20<|≤25

S(Cu) mm(2)

1

1.5

2.5

4

Next, use wire strippers to strip 9 to 11 mm of the copper wire, ensuring clean and precise preparation.

5. Connections

Use wire crimping pliers to crimp wire noses onto the copper wire ends. For NQ3 incoming and outgoing wires, pass the wires through the waterproof connector.

Then, tighten the nylon waterproof cable connector.

Identify the primary circuit incoming terminals (contactors 1/L1, 3/L2, and 5/L3) and outgoing terminals (thermal relays 2/T1, 4/T2, and 6/T3). Refer to this table for torque value:

Model Number

NQ3-11P

Fastening Screw Size

M3.5

M4

Tightening Torque (N.m.)

1.2

6. Grounding

Connect the ground wire to the ground screw on the base and tighten securely to establish a proper electrical safety connection.

7. Finalization

Tighten the waterproof connector nut to ensure the rubber inside grips the wire. The aim is to ensure it provides robust protection against environmental factors.

How to Test the NQ3

Test the DOL starter to make sure it functions correctly. Here are key testing guidelines:

  • Before powering on, confirm the smooth operation of the STOP and RESET buttons by manually pressing and checking their responsiveness.
  • Set thermal relay current value 10-15% below the motor’s rated working current for initial calibration.
  • Monitor direct online starter performance during initial test run, watching for any unusual vibrations or sounds.
  • Gradually increase the current setting if the motor starter operates without unexpected tripping or overload.
  • After powering on, use a multimeter to perform a continuity test across AC contactor terminals, checking for proper electrical connectivity.
  • After successful debugging, carefully reassemble the upper cover and base, ensuring all screws are tightened securely.

Troubleshooting Guide

Potential issues can arise during DOL starter installation or operation. Here are detailed case studies with troubleshooting approaches:

Analysis and Troubleshooting of Common Faults

Symptom

Cause Analysis

Troubleshooting Methods

The starter malfunctions prematurely without overload

The current value of the thermal relay is smaller than the actual working current of the motor

Fine-tune the current dial to match the product's current value with the actual motor current value

Strong shock or vibration

Check the installation site, eliminate faults, and ensure that the product is not exposed to strong shock or vibration

Frequent motor starting

The motor needs to be started at certain intervals, and the frequency should not exceed 30 times/hour

The cross-sectional area of the primary circuits connecting wire is too small

Select standard wire according to Table 4

The starter does not work due to overload

The current value of the thermal relay is greater than the actual working current of the motor

Fine-tune the current dial to match the product's current value with the actual motor current value

The cross-sectional area of the primary circuit connecting wire is too large

Select standard wire according to Table 4

Starter not working

The starter wiring is loose or detached

Tighten the wiring screws and check whether the screws are loose

The coil voltage is too low or fluctuates too much

Increase the power supply voltage or add voltage stabilizing device

The current value of the thermal relay is too small, and the product does not reset

Tune the current dial towards the high current direction

The contact is not energized

Return to the manufacturer for repair

Conclusion

Installing an NQ3 DOL starter requires precision, careful preparation, and a systematic approach. By following these detailed guidelines, you can ensure a safe and efficient installation. If you are encountering issues or have queries, feel free to consult our technical support team at CHINT. Browse our website to explore our motor starters and electrical solutions.

The Latest
JUNE 12, 2025 What Is Motor Start Up Current and Why Is It So High?

Discover why motor start-up current is so high and how it affects electrical systems. Learn how to protect motors effectively with CHINT's solutions.

JUNE 12, 2025 Selecting the Right Air Circuit Breaker for Data Centers and Critical Power Distribution Site

Discover how to select the right air circuit breaker for data centers. Learn about CHINT’s NA8 features, certifications, and smart integration benefits.

JUNE 11, 2025 Everything You Should Know About Solar Pumping System

Understand the benefits, applications, and components of solar pumping systems including CHINT’s NVFPV drives for reliable water access.

JUNE 10, 2025 How Altitude Affects the Performance of Moulded Case Circuit Breakers

Learn the effects of altitude on circuit breakers and explore CHINT’s NM8N-HV MCCB built for extreme conditions with high performance and safety.

JUNE 9, 2025 What Is A Pulse Relay and How Does It Work?

Explore the energy-efficient pulse relay technology used in automation, lighting, and security systems. Featuring CHINT’s NJMC1 relay for reliable performance.

JUNE 7, 2025 Understanding AC Contactors: Uses and Warning Signs of Failure

Learn how to recognize signs of a failing AC contactor and get expert tips on resolving issues, performing maintenance, and ensuring electrical safety.

JUNE 6, 2025 What Are Harmonics and Total Harmonic Distortion (THD) in Power Systems

Discover the causes, impacts, and solutions for harmonics and THD in electrical networks. Enhance reliability with CHINT’s NZB379 controller.

JUNE 6, 2025 Types of Lightning Surge Arresters and Their Functions

Discover the essential types of lightning surge arresters and their working principles. Learn how to protect your electrical systems from voltage surges effectively.

JUNE 5, 2025 Thermal Magnetic Circuit Breakers vs Hydraulic Magnetic Circuit Breakers

A comprehensive comparison of thermal magnetic and hydraulic magnetic circuit breakers. Learn about their protection, environmental susceptibility, trip time, size, and cost with CHINT.

JUNE 5, 2025 Automatic Transfer Switch (ATS) Comprehensive Guide

Explore how ATS ensures uninterrupted power supply for critical applications. Learn about types, uses, performance, and CHINT solutions.